Network Connection Tests 1. I disconnected the ethernet cable from HalldEN2T1, which is in Backplane 0 with the PLC a. HMI lost connection, because this is the RSLinx Enterprise connection b. RSLogix5000 lost connection because RSLinx was lost. c. All I/O modules in Backplane 3 had a red light in the "OK" window indicating faulty communications 2. I plugged the ethernet cable back in a. RSLinx Enterprise reconnected automatically b. I/O modules in Backplane 3 had "OK" lights go to green c. I was able to go back "online" with RSLogix5000 3. I unplugged the ethernet cable from HalldEN2T2, which is in Backplane 3 a. All I/O modules in Backplane 3 had red light in "OK" window b. RSLogix5000 reported that the module was not connected 4. I plugged the ethernet cable back in a. I/O modules in Backplane 3 went from red to green b. RSLogix5000 reconnected with the module automatically 5. I unplugged the EWEB module a. Display screen displayed "LINK LOST" b. No other indication of failure 6. I plugged EWEB back in a. Display changed to "OK" 7. I unplugged the ethernet cable from the back of halldsc5 a. All data in HMI went blank b. No HMI control available -- nothing worked. 8. I plugged the ethernet cable back into halldsc5 a. HMI Software indicated that ethernet connectivity was restored, but HMI Control was not automatically restored b. I checked the status of the HMI Server and the RSLinx Enterprise server. HMI Server was running, but RSLinx Enterprise Server (hosted on halldsc2) was "unreachable" c. I tried to ping halldsc2 from halldsc5 and the request timed out d. I tried to ping halldsc5 from halldsc2 - I was successful e. I logged out of halldsc5 and logged in again. Tried to ping halldsc2 - unsuccessful f. I restarted halldsc5. Still unable to ping halldsc2 g. I restared halldsc2. I was able to ping halldsc2 from halldsc5 and RSLinx Enterprise came back online. 9. I unplugged the ethernet cable from halldsc2 a. HmI data went blank 10. I plugged the ethernet cable back into halldsc2 a. HMI software did not recover. It indicated that halldsc2 was "unreachable" b. Tried to ping halldsc2 from halldsc5 - unsuccessful c. Tried to ping halldsc5 from halldsc2 - successful d. Logged out and back into halldsc2 - still "unreachable" e. Rebooted halldsc2. After some time, its status changed to "Active", HMI control was restored.