Difference between revisions of "Forward Multi-Wire Proportional Chambers Shift"

From Hall D Ops Wiki
Jump to: navigation, search
(The Multi-Wire Proportional Chambers)
(Expert personnel)
 
(36 intermediate revisions by the same user not shown)
Line 1: Line 1:
== The Multi-Wire Proportional Chambers and Central Time-of-Flight==
 
  
The Forward Drift Chamber (FDC)  system consists
+
[[Image:Muon detector sketch.png | thumb | 400px | Fig. 1. Sketch of muon detector. ]]
of four identical packages (named FDC1 to FDC4), each having six chambers or cells (named CELL1 to CELL6).
+
These are planar drift chambers with both anode wires and cathode strips being readout,
+
in total 12,672 channels.
+
  
The cells within a package
+
In this section we combine the information about the FMWPCs and the CTOF, as they together form the active detectors for the Hall D muon detector. In addition a common GUI was developed for both due to the small number of scintillator channels. A sketch of the muon detector is shown in Fig. 1.
have independent gas volumes, but are separated with a flexible mylar membrane.
+
Therefore,  <font color=red> the pressure difference between neighboring cells should never exceed 30 Pa </font> and should normally be less than 5 Pa. Note that
+
the interlock should safeguard against excessive differential pressure.
+
+
Positive (up to 2200 V) and negative (up to 500 V) HV is applied on the
+
sense and field wires respectively with <font color=red> currents not exceeding 3 microA per HV channel</font> .
+
  
The detector (including cables) emits a total power of about 1500 Watt,
+
== The Multi-Wire Proportional Chambers (FMWPC) ==
of which about 900 Watt inside the magnet,
+
due to the LV applied on the detector pre-amplifieres.
+
A cooling system using Fluorinert is used to keep the temperature on the
+
pre-amplifiers within the permissible limits. <font color=red> The LV system should never be turned ON if the cooling system doesn't work </font>.
+
The interlock should safeguard against this condition.
+
  
Details can be found in [https://halldweb.jlab.org/DocDB/0050/005080/001/MWPC_writeup_for_ERR.pdf MWPC Construction Report]
+
The Forward Multi-Wire Proportional Chamber (FMWPC)  system consists of six planes interspersed between iron absorbers, which are located downstream of the FCAL on the downstream platform. Three chambers have vertical wires and three have horizontal wires. Each plane consists of 144 sense wires, operating at the nominal +1800 V. The preamps, located on the chambers are powered with +/- 5 V. The table provides a summary of the basic chamber properties.  Additional details can be found in the [https://halldweb.jlab.org/DocDB/0050/005080/001/MWPC_writeup_for_ERR.pdf MWPC Construction Report].
 +
 
 +
{| class="wikitable" style="text-align: left;"
 +
|+ MWPC Characteristics
 +
|-
 +
! Parameter  !! Value
 +
|-
 +
| style="text-align:left" | sensitive area  ||  60 x 60 inch2
 +
|-
 +
| style="text-align:left" |  sense wire pitch ||  0.4 inch
 +
|-
 +
| style="text-align:left" |wire plane to cathode plane distance ||  0.4 inch
 +
|-
 +
| style="text-align:left" |size of central deadened region ||  10 x 10 cm2
 +
|-
 +
| style="text-align:left" |wire arrangement ||  planar, with field wires between sense wires
 +
|-
 +
| style="text-align:left" | sense wire diameter  ||  20 um
 +
|-
 +
| style="text-align:left" | field wire diameter  ||  .003” non-central region, .004” central region
 +
|-
 +
| style="text-align:left" | sense wire voltage  ||  typically +1800 Volt
 +
|-
 +
| style="text-align:left" |  field wire voltage ||  ground
 +
|-
 +
| style="text-align:left" |  cathode plane voltage ||  ground
 +
|-
 +
| style="text-align:left" |  operating gas ||  90:10 argon:CO2 by volume, flowing at 5 cc/s
 +
|-
 +
| style="text-align:left" | typical chamber gain  ||  about 100,000
 +
|-
 +
| style="text-align:left" |  maximum drift time ||  about 570 ns
 +
|-
 +
| style="text-align:left" | number of electronic channels per chamber  ||  144
 +
|}
 +
 
 +
== Central Time-of-Flight (CTOF)  ==
 +
 
 +
The Central Time-of-Flight system consists of a single plane of plastics scintillators located downstream of the last FMWPC. The plane consists of four scintillators hung vertically, placed symmetrically relative to the beamline,  two on each side. Each counter consists of an active scintillator area of 1.27x20x120 cm3 with light guides on top and bottom connected to XP2262B pmts. The typical voltage is -1700 V. Each of the eight pmts has two outputs, supplying signals to the FADC250s and discriminators that feed CAEN TDCs, scalers and trigger logic that generate the Front-Panel CTOF trigger. The CTOF trigger consists of a logic AND of top and bottom pmts for each counter and a logic OR of the four counter coincidences.
  
 
== Routine operation==
 
== Routine operation==
  
[[Image:FMWPC_epics_screen.png | thumb | 400px | Fig. 1. FMWPC HV, LV GUI panel. ]]
+
[[Image:FMWPC_epics_screen.png | thumb | 400px | Fig. 2. FMWPC HV, LV GUI panel. ]]
  
The most important task for the shift workers is to monitor the parameters (using GUIs) and report any changes from the normal operation for the following FDC related subsystems: High Voltage, Low Voltage (including thresholds), Gas system, and the Cooling system.  A description of how to bring up the corresponding GUI screens and how to operate them can be found in [[Slow Controls Shift| Section Slow Controls]]. The HV and LV subsystems, as well as the Gas and Cooling systems have common GUIs. The GUIs are designed to show green color if all the parameters in a certain subsystem/subgroup are within the limits. If any of the parameters is out of limits the background for the corresponding subsystem/subgroup will turn red. Examples of the GUIs are shown in Figs. 1 and 2.
+
The most important task for the shift workers is to monitor the parameters (using GUIs) and report any changes from the normal operation for the HV and LV of the FMWPC and CTOF systemsBoth systems are controlled using a single GUI. A description of how to bring up the corresponding GUI screens and how to operate them can be found in the[[Slow Controls Shift| Section Slow Controls]]. The HV and LV subsystems have a common GUI. The GUIs are designed to show green color if all the parameters in a certain subsystem/subgroup are within their operating limits. If any of the parameters is out of limits the background for the corresponding subsystem/subgroup will turn red. An example the GUI is shown in Figs. 2 for normal operating conditions.
  
The shift workers are allowed, using the GUI, to turn ON and OFF all the HV and LV (including thresholds) systems, as well as parts of them or the individual channels. Instructions how to do this are given in [[Slow Controls Shift| Section Slow Controls]], but the general rule is either to bring the pop-up menu with left click on the group title (like "ALL HV", or "FDC 1") or to click on the individual channel knob (the knob title shows the action to be taken after pressing it). For example, in case a HV channel trips, one should press the corresponding channel knob once (acknowledging the trip)  and then again to turn it on. The corresponding voltage parameters, like rump up/down rates, trip currents, set voltage values etc. cannot be changed by the shift workers. The Gas and cooling system GUI is only to be monitored by the shift workers; the parameters there cannot be changed.  
+
The shift workers are allowed, using the GUI, to turn ON and OFF all the HV and LV systems, as well as parts of them or the individual channels. Instructions how to do this are given in [[Slow Controls Shift| Section Slow Controls]], but the general rule is either to bring the pop-up menu with left click on the group title (like "ALL OFF ALL HV / LV") or to click on the individual channel knob (the knob title shows the action to be taken after pressing it). For example, in case a HV channel trips, one should press the corresponding channel knob once (acknowledging the trip)  and then again to turn it on. The corresponding voltage parameters, like ramp up/down rates, trip currents, set voltage values etc. should not be changed by the shift workers. The restoration of voltage settings to nominal operation can be accomplished using the top right button "SAVE/RESTORE."
  
In addition to the operations using GUIs, the shift workers should visually check the gas panel in the Hall using the camera "halldaxis7" with remote control installed there, and make sure all the bubblers operate normally. For instructions how to operate the camera, refer to [[Slow Controls Shift| Section Slow Controls]]. Once per shift the workers are supposed to record the manometer values and inspect other components in the gas room; see [[Gas System Shift| Section Gas System]].
+
The FMWPCs operate with pre-mixed 90/10 Ar/CO2 bottles located in the gas racks outside the hall. The gas flow to each plane is controlled via manually adjustable flow meters located on each chamber. The flow rate will be set at the beginning of the run by experts, but the flow rate can be viewed remotely by either the east wall "halldcam3" or the south wall "south-cam" cameras. For instructions how to operate the camera, refer to [[Slow Controls Shift| Section Slow Controls]]. The shift the workers should  record the gas flow for each chamber once per shift.
  
 
'''Operations beyond what is specified above shall only be performed by the system expert or under his/her direction'''.
 
'''Operations beyond what is specified above shall only be performed by the system expert or under his/her direction'''.
Line 37: Line 60:
 
== Interlocks==
 
== Interlocks==
  
To prevent damage of the equipment in situations explained in the first paragraph (where the corresponding critical parameter limits were highlighted with red) interlock systems are implemented. Hardware interlock is used to turn OFF the power of the LV crate in case the cooling system fails. Software (PLC based) interlock system  is implemented to turn off the gas supply if the pressure between any two neighboring cells exceeds 30 Pa. The HV and LV modules are set to immediately turn off the voltage if the current exceeds the corresponding limit. Setting the voltage channel back should be done only manually by the operator. We DO NOT use the automatic feature to keep the voltage (for a certain time) such that the current is at the limit.
+
The HV and LV modules are set to immediately turn off the voltage if the current exceeds the corresponding limit. Setting the voltage channel back should be done only manually by the operator.
  
 
== Expert personnel ==
 
== Expert personnel ==
  
The individuals responsible for the operation of the FDC are shown in the following table.
+
The individuals responsible for the operation of the FMWPCs are shown in the following table.
 
Problems with normal operation of the FDC should be referred to those individuals and any changes to their settings must be
 
Problems with normal operation of the FDC should be referred to those individuals and any changes to their settings must be
 
approved by them. Additional experts may be trained by the system owner and their name and date added to this table.
 
approved by them. Additional experts may be trained by the system owner and their name and date added to this table.
  
 
  {| border=1  
 
  {| border=1  
|+ Table:  Expert personnel for the FDC system
+
|+ Table:  Expert personnel for the FMWPC and CTOF systems
 
|- bgcolor=#DFDFDF   
 
|- bgcolor=#DFDFDF   
 
! width=200px | Name    !!  width=100px | Extension !! Date of qualification  
 
! width=200px | Name    !!  width=100px | Extension !! Date of qualification  
 
|-
 
|-
| Lubomir Pentchev   ||  align=center | 269-5470   ||  align=center | June 3, 2014
+
| Beni Zihlmann   ||  align=center | 269-5310   ||  align=center | May 20, 2022
 +
|-
 +
| Rory Miskimen  || align=center | 413-824-6293 || align=center | May 20, 2022
 
  |}
 
  |}

Latest revision as of 14:36, 11 May 2022

Fig. 1. Sketch of muon detector.

In this section we combine the information about the FMWPCs and the CTOF, as they together form the active detectors for the Hall D muon detector. In addition a common GUI was developed for both due to the small number of scintillator channels. A sketch of the muon detector is shown in Fig. 1.

The Multi-Wire Proportional Chambers (FMWPC)

The Forward Multi-Wire Proportional Chamber (FMWPC) system consists of six planes interspersed between iron absorbers, which are located downstream of the FCAL on the downstream platform. Three chambers have vertical wires and three have horizontal wires. Each plane consists of 144 sense wires, operating at the nominal +1800 V. The preamps, located on the chambers are powered with +/- 5 V. The table provides a summary of the basic chamber properties. Additional details can be found in the MWPC Construction Report.

MWPC Characteristics
Parameter Value
sensitive area 60 x 60 inch2
sense wire pitch 0.4 inch
wire plane to cathode plane distance 0.4 inch
size of central deadened region 10 x 10 cm2
wire arrangement planar, with field wires between sense wires
sense wire diameter 20 um
field wire diameter .003” non-central region, .004” central region
sense wire voltage typically +1800 Volt
field wire voltage ground
cathode plane voltage ground
operating gas 90:10 argon:CO2 by volume, flowing at 5 cc/s
typical chamber gain about 100,000
maximum drift time about 570 ns
number of electronic channels per chamber 144

Central Time-of-Flight (CTOF)

The Central Time-of-Flight system consists of a single plane of plastics scintillators located downstream of the last FMWPC. The plane consists of four scintillators hung vertically, placed symmetrically relative to the beamline, two on each side. Each counter consists of an active scintillator area of 1.27x20x120 cm3 with light guides on top and bottom connected to XP2262B pmts. The typical voltage is -1700 V. Each of the eight pmts has two outputs, supplying signals to the FADC250s and discriminators that feed CAEN TDCs, scalers and trigger logic that generate the Front-Panel CTOF trigger. The CTOF trigger consists of a logic AND of top and bottom pmts for each counter and a logic OR of the four counter coincidences.

Routine operation

Fig. 2. FMWPC HV, LV GUI panel.

The most important task for the shift workers is to monitor the parameters (using GUIs) and report any changes from the normal operation for the HV and LV of the FMWPC and CTOF systems. Both systems are controlled using a single GUI. A description of how to bring up the corresponding GUI screens and how to operate them can be found in the Section Slow Controls. The HV and LV subsystems have a common GUI. The GUIs are designed to show green color if all the parameters in a certain subsystem/subgroup are within their operating limits. If any of the parameters is out of limits the background for the corresponding subsystem/subgroup will turn red. An example the GUI is shown in Figs. 2 for normal operating conditions.

The shift workers are allowed, using the GUI, to turn ON and OFF all the HV and LV systems, as well as parts of them or the individual channels. Instructions how to do this are given in Section Slow Controls, but the general rule is either to bring the pop-up menu with left click on the group title (like "ALL OFF ALL HV / LV") or to click on the individual channel knob (the knob title shows the action to be taken after pressing it). For example, in case a HV channel trips, one should press the corresponding channel knob once (acknowledging the trip) and then again to turn it on. The corresponding voltage parameters, like ramp up/down rates, trip currents, set voltage values etc. should not be changed by the shift workers. The restoration of voltage settings to nominal operation can be accomplished using the top right button "SAVE/RESTORE."

The FMWPCs operate with pre-mixed 90/10 Ar/CO2 bottles located in the gas racks outside the hall. The gas flow to each plane is controlled via manually adjustable flow meters located on each chamber. The flow rate will be set at the beginning of the run by experts, but the flow rate can be viewed remotely by either the east wall "halldcam3" or the south wall "south-cam" cameras. For instructions how to operate the camera, refer to Section Slow Controls. The shift the workers should record the gas flow for each chamber once per shift.

Operations beyond what is specified above shall only be performed by the system expert or under his/her direction.

Interlocks

The HV and LV modules are set to immediately turn off the voltage if the current exceeds the corresponding limit. Setting the voltage channel back should be done only manually by the operator.

Expert personnel

The individuals responsible for the operation of the FMWPCs are shown in the following table. Problems with normal operation of the FDC should be referred to those individuals and any changes to their settings must be approved by them. Additional experts may be trained by the system owner and their name and date added to this table.

Table: Expert personnel for the FMWPC and CTOF systems
Name Extension Date of qualification
Beni Zihlmann 269-5310 May 20, 2022
Rory Miskimen 413-824-6293 May 20, 2022